Ref. Std. EIA RS 485 KPE Insulated, Individual And General Screen Data Cables |
Application
This sort of cables are used as signal and transmission cables in the electronical control systems and also in the transmission of voice frequency. Their halogen-free counterparts are distinguished with flame retarding and low smoke features. |
Construction
1. | Inner Conductor | Electrolytic twisted tinned copper wire (EN 60228, Class 2/5) |
2. | Insulation | Foam-Skin PE (EN 50290-2-23) |
3. | Pair Screen | The cable cores insulated as per Table 1 are twisted in pair, twisted pair cores are fixed with PES tape, They are screened with both multiple tinned drain wire and also with %100 covered AL-PES tape |
4. | Lay-Up | Screened pairs twisted in layers, fixed with PES tape, |
5. | Overall Screen | They are screened with multiple, tinned drain wire and %100 covered AL-PES tape |
6. | Braiding Screen | Tinned copper wire braid screen coverage ratio is %85 ± 5 |
7. | Outer Sheath | PVC (EN 50290-2-22) HFFR (EN 50290-2-27) RAL 7032, Grey HFFR (EN 50290-2-27) RAL 7032, Grey |
General Features
Flame Retardent (For Single Cable) |
IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2 | |
Halogen Acid Gas Test | IEC 60754-1, EN 50267-2-1, VDE 0482-267-2-1 | |
Acidic (Corrosive) Gas Test |
IEC 60754-2, EN 50267-2-2, VDE 0482-267-2-2 | |
Smoke Density Test | IEC 61034-2, EN 61034-2, VDE 0482-1034-2 |
Technical Properties
Temperature Range | Fixed -30 °C …. +80 °C / Flexible -5 °C …. +70 °C | |
Operating Voltage | 250 V | |
Test Voltage | core – core 1200 V, core – screen 1000 V | |
Min. Bending Radius | Fixed 7,5xD / Flexible 12xD |
Documents
RS 485 / KD-5530 LI-O2YS(St)CY-PIMF PVC/HFFR/PE |