RS 485 / KD-5130 LI-O2YS(St)Y-TP PVC/HFFR/PE

Ref. Std. EIA RS 485
KPE Insulated, General Screen Data Cables

RS 485 / KD-5130 LI-O2YS(St)Y-TP<br />
PVC/HFFR/PE

Application
This sort of cables are used as signal and transmission cables in the electronical control systems and also in the transmission of voice frequency. Their
halogen-free counterparts are distinguished with flame retarding and low smoke features.
Construction
1. Inner Conductor Electrolytic twisted tin-plated copper wire (EN 60228, Class 2/5)
2. Insulation Foam-Skin PE (EN 50290-2-23)
3. Lay-Up Cable cores which are isolated with respect to the table 1, are twisted in pairs following that, those pairs are
twisted in layers and at the end, they are fixed with pes-tape
4. Overall Screen They are screened with 100% coverage multiple tin-copper drain wire AL-PES tape
5. Outer Sheath PVC (EN 50290-2-22),
HFFR (EN 50290-2-27), RAL 7032, GreyHFFR (EN 50290-2-27), RAL 7032, Grey
General Features
Flame Retardent
(For Single Cable)
IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2
Halogen Acid Gas Test IEC 60754-1, EN 50267-2-1, VDE 0482-267-2-1
Acidic (Corrosive)
Gas Test
IEC 60754-2, EN 50267-2-2, VDE 0482-267-2-2
Smoke Density Test IEC 61034-2, EN 61034-2, VDE 0482-1034-2
Technical Properties
Temperature Range Fixed -30 °C …. +80 °C / Flexible -5 °C …. +70 °C
Operating Voltage 250 V
Test Voltage core – core 1200 V, core – screen 1000 V
Min. Bending Radius Fixed 7,5xD / Flexible 12xD
Documents
 RS 485 / KD-5130 LI-O2YS(St)Y-TP
PVC/HFFR/PE