EN 50288-7 Multi-Core, Overall Screened, Round Steel Wire Armoured Signalization Cables 300 V – 500 V |
Application
These cables are generally employed in instrumentation and control systems, analog and digital signal transmission of chemical and petrochemical industrial premises, power plants, natural gas and petroleum industries, etc. Direct connection is not permitted under ambient with a low impedance sources. Cables with blue sheaths are suitable for security system applications. The cable armour protects the cable against mechanical impacts. Furthermore, these cables can directly be buried in the soil. They are suitable in dry and wet indoor and outdoor installations. |
Construction
1. | Inner Conductor | Electrolytic stranded annealed copper wire (IEC 60228, Class 2) |
2. | Insulation | Y : PVC (EN 50290-2-21) 2Y : PE (EN 50290-2-23) 2X : XLPE (EN 50290-2-29) |
3. | Lay-Up | Cores are twisted in layers. Fixed with PES tape. |
4. | Overall Screening | (St) : %100 Coverage AL-PES tape and 0,50 mm² (7×0,30 mm) tinned strand drain wire with screened. |
5. | Inner Sheath | Y : PVC sheath (EN 50290-2-22) |
6. | Armouring | SWA : Round galvanized steel wire armours |
7. | Outer Sheath | Y : PVC Sheath (EN 50290-2-22), RAL 9005 Black, RAL 5015 Blue or RAL 7001 Grey |
General Features
Flame Retardent (For Single Cable) |
IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2 | |
Flame Retardent (For a Bunch of Cable) | IEC 60332-3-24, EN 60332-3-24, VDE 0482-332-3-24 | |
Determination of (Test of determination of flaming droplets) | IEC 60332-1-3, EN 60332-1-3, VDE 0482-332-1-3 | |
Oil Resistance | ICEA S-82-552 | |
UV Resistance | Only valid for Black sheath cables. |
Technical Properties
PVC (Y) / PE (2Y) / XLPE (2X) | ||
Temperature Range | Fixed -30 °C …. +70 °C / Flexible -5 °C …. +50 °C / Fixed -30 °C …. +70 °C / Flexible -5 °C …. +50 °C / Fixed -30 °C …. +90 °C / Flexible -5 °C …. +50 °C | |
Min. Bending Radius | 10xD |
Documents
RE-Y(St)YSWAY-fl MC RE-2Y(St)YSWAY-fl MC RE-2X(St)YSWAY-fl MC |