EN 50288-7 Multi-Pair, Individual and Overall Screened, Round Steel Wire Armoured, Instrumentation Cables 300 V-500 V |
Application
These cables are generally employed in instrumentation and control systems, analog and digital signal transmission of chemical and petrochemical industrial premises, power plants, natural gas and petroleum industries, etc. Direct connection is not permitted under ambient with a low impedance sources. Cables with blue sheaths are suitable for security system applications. Furthermore, these cables can directly be buried in the soil. They are suitable in dry and wet indoor and outdoor installations. |
Construction
1. | Inner Conductor | Electrolytic stranded annealed copper wire (IEC 60228, Class 2) |
2. | Insulation | 2Y : PE (EN 50290-2-23) 2X : XLPE (EN 50290-2-29) |
3. | Individual Screen | PIMF : Dual cores are fixed with PES tape 0,60 mmØ with screened mono tinned drain wire and AL-PES tape. TIMF : Triple cores are fixed with PES tape, 0,60 mmØ mono tinned drain wire and AL-PES tape with screened.. |
4. | Communication Core | 0,50 mm² (7×0,30 mm) Tinned or annealed stranded copper, PE or XLPE insulated orange core. (Multi pair or triple cables) |
5. | Lay-Up | Screened pair cores are strand communication core with together twisted layers. Fixed with PES tape. |
6. | Overall Screening | (St) : %100 coverage AL-PES tape and 0,50 mm² (7×0,30 mm) screened with tinned strand drain wire. |
7. | Inner Sheath | H : HFFR sheath (EN 50290-2-27) |
8. | Armouring | SWA : Round galvanized steel wire armour |
9. | Outer Sheath | H : HFFR Sheath (EN 50290-2-27), RAL 9005 Black, RAL 5015 Blue or RAL 7001 Grey |
General Features
Flame Retardent (For Single Cable) |
IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2 | |
Flame Retardent (For a Bunch of Cable) | IEC 60332-3-24, EN 60332-3-24, VDE 0482-332-3-24 | |
Determination of (Test of determination of flaming droplets) | IEC 60332-1-3, EN 60332-1-3, VDE 0482-332-1-3 | |
Halogen Acid Gas Test | IEC 60754-1, EN 50267-2-1, VDE 0482-267-2-1 | |
Acidic (Corrosive) Gas Test |
IEC 60754-2, EN 50267-2-2, VDE 0482-267-2-2 | |
Smoke Density Test | IEC 61034-2, EN 61034-2, VDE 0482-1034-2 | |
Oil Resistance | ICEA S-82-552 | |
UV Resistance | Only valid for Black sheath cables.. |
Technical Properties
PE (2Y) / XLPE (2X) | ||
Temperature Range | Fixed -30 °C …. +70 °C / Flexible -5 °C …. +50 °C / Fixed -30 °C …. +90 °C / Flexible -5 °C …. +50 °C | |
Min. Bending Radius | 10xD |
Documents
RE-2Y(St)HSWAH-fl PIMF / TIMF RE-2X(St)HSWAH-fl PIMF / TIMF |