Ref. Std. VDE 0812 HFFR Signal, Control Cables |
Application
These cable are used to electronic control systems connection, voice frequency transmission, signal and communication cables Halogen free cables have flame retardant properties and low smoke density. |
Construction
1. | Inner Conductor | Electrolytic stranded annealed copper wire (IEC 60228, VDE0295, HD383, Class 5) |
2. | Insulation | HFFR Insulation (EN 50290-2-26, VDE0207-HI2) |
3. | Lay-Up | According to DIN 47100 colors insulated cores twisted in layers |
4. | Outer Sheath | HFFR (EN 50290-2-27, VDE0207-HM2), RAL 7001, Grey |
General Features
Flame Retardent (For Single Cable) |
IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2 | |
Flame Retardent (For a Bunch of Cable) | IEC 60332-3-24, EN 60332-3-24, VDE 0482-332-3-24 | |
Determination of (Test of determination of flaming droplets) | IEC 60332-1-3, EN 60332-1-3, VDE 0482-332-1-3 | |
Halogen Acid Gas Test | IEC 60754-1, EN 50267-2-1, VDE 0482-267-2-1 | |
Acidic (Corrosive) Gas Test |
IEC 60754-2, EN 50267-2-2, VDE 0482-267-2-2 | |
Smoke Density Test | IEC 61034-2, EN 61034-2, VDE 0482-1034-2 |
Technical Properties
Temperature Range | Fixed -30 °C …. +70 °C Flexible -5 °C …. +70 °C | |
Min. Bending Radius | Fixed 7,5xD Flexible 15xD |
Documents
LIHH |