Ref. Std. VDE 0815 HFFR Industrial Electronics Internal Installation Cables |
Application
These cables are used fixed indoor installation and signal transmission. The screen protects the cable core against electrical noises and interferences. Halogen free cables are flame retardent features and low smoke density |
Construction
1. | Inner Conductor | Electrolytic mono annealed copper (IEC 60228, VDE 0295 Class 1) |
2. | Insulation | HFFR (EN 50290-2-26, VDE 0207 HI2) Cable colors according to VDE 0815; |
3. | Lay-Up | Pair layout cores are twisted with 4 unit, 4 units are twisted in as layers. Fixed with PES Tape |
4. | Screen | AL-PES tape with together (0,80 mmØ) mono tinned copper or mono annealed copper drain wire with screened. |
5. | Outer Sheath | HFFR(EN 50290-2-27,VDE0207 HM2), RAL 7032 Grey |
General Features
Flame Retardent (For Single Cable) |
IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2 | |
Flame Retardent (For a Bunch of Cable) | IEC 60332-3-24, EN 60332-3-24, VDE 0482-332-3-24 | |
Determination of (Test of determination of flaming droplets) | IEC 60332-1-3, EN 60332-1-3, VDE 0482-332-1-3 | |
Halogen Acid Gas Test | IEC 60754-1, EN 50267-2-1, VDE 0482-267-2-1 | |
Acidic (Corrosive) Gas Test |
IEC 60754-2, EN 50267-2-2, VDE 0482-267-2-2 | |
Smoke Density Test | IEC 61034-2, EN 61034-2, VDE 0482-1034-2 |
Technical Properties
Temperature Range | -30 °C …. +70 °C | |
Operating Voltage | Max. 225 V | |
Test Voltage | Core/core 500 V, core/screen 2000 V | |
Min. Bending Radius | 10xD |
Documents