Ref. Std. HD 21.13 S1, DIN VDE 0281 part 13 Oil Resistance PVC Sheath Braid Screen Control Cables |
Application
Such cables are suitable for use in machine production for measuring, imaging and control purposes, in power stations, engineering projects and HVAC and similar electrical systems under dry or moist ambient, in particular suited to the industrial environments. Theese cables not used open air, outdoor environments. |
Construction
1. | Inner Conductor | Electrolytic stranded annealed copper wire (IEC 60228, VDE0295, HD383, Class 5) |
2. | Insulation | PVC TI2 tipi, HD 21.1.S4suitable |
3. | Lay-Up | According to VDE 293 insulated cores twisted in layers. From 3 cores Yellow / Green line is drain core. |
4. | Inner Sheath | PVC,TM2 tipi, HD 21.1.S4suitable |
5. | Screen | Tinned copper wire Braid Screen, HD 21.13 S1suitable. |
5. | Outer Sheath | PVC,TM5 tipi, HD 21.1.S4suitable, RAL 7001, Grey |
General Features
Flame Retardent (For Single Cable) |
IEC 60332-1, EN 60332-1, VDE 0482-332-1 | |
Oil Resistance | HD 22.10.S1, VDE 0282-10 |
Technical Properties
Temperature Range | Fixed -40 °C …. +70 °C Flexible -5 °C …. +70 °C | |
Operating Voltage | 300/500 V | |
Test Voltage | 2000 V, 5 dk | |
Short Circuit Temperature Range | Max. 160 °C | |
Min. Bending Radius | 10xD |
Documents
H05VVC4V5-K / (NYSLYCYÖ-JZ) |