NHMH 300/500 V

Ref. Std. VDE 0250-215
Multi-Core, one or LSOH Multi Wire Power Cables

NHMH 300/500 V

Application
Used in large hotels, hospitals, shopping centers, power plants and data processing centers as well as in facilities where mass transportation is made
through rail systems, including numerous people and valuable devices and exposed to fire risk. These cables do not transport flames during fire, do not produce an
intense vapor/smoke layer, nor do they create an environment convenient for corrosion, therefore ensure life and material safety.
Construction
1. Inner Conductor Electrolytic mono or stranded annealed copper wire (EN 60228 Class 1/2, VDE 0295)
2. Insulation Halogen-free thermoplastic material
3. Lay-Up VDE 0293-308 & HD 308 Cores which are isolated in accordance with S2 are bent in layers at fixed steps.
4. Common Sheath HFFR They are encased with fill material in round form and easy to strip.
5. Outer Sheath HFFR, Halogen-free polymer material HM5, RAL 7001, Grey
General Features
Flame Retardent
(For Single Cable)
IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2
Flame Retardent (For a Bunch of Cable) IEC 60332-3-24, EN 60332-3-24, VDE 0482-332-3-24
Determination of (Test of determination of flaming droplets) IEC 60332-1-3, EN 60332-1-3, VDE 0482-332-1-3
Halogen Acid Gas Test IEC 60754-1, EN 50267-2-1, VDE 0482-267-2-1
Acidic (Corrosive)
Gas Test
IEC 60754-2, EN 50267-2-2, VDE 0482-267-2-2
Smoke Density Test IEC 61034-2, EN 61034-2, VDE 0482-1034-2
Technical Properties
Temperature Range (°C) max. -20 °C …. +70 °C
Short Circuit Temperature 160 °C
Nominal Voltage (Uo/U) 300/500 V
Min. Bending Radius 12xD
Documents