RE-2G(St)H-CI MC FE-180 PH90

EN 50288-7
Multi-Core, Overall Screen, Fire Resistant Signaling Cables
300 V-500 V

RE-2G(St)H-CI MC FE-180 PH90

Application
These cables are generally employed in instrumentation and control systems, analog and digital signal transmission of chemical and petrochemical industrial
premises, power plants, natural gas and petroleum industries, etc. Direct connection is not permitted under ambient with a low impedance sources. Cables with blue sheaths are
suitable for security system applications. Furthermore, these cables can directly be buried in the soil. They are suitable in dry and wet indoor and outdoor installations.
Construction
1. Inner Conductor Electrolytic stranded annealed copper wire (IEC 60228, Class 2)
2. Insulation Silicone Rubber (HD 22.1, EI2)
3. Lay-Up Cores are twisted in layers. Fixed with PES tape.
4. Overall Screening %100 Coverage AL-PES tape ve 0,50 mm² (7×0,30 mm) screened with tinned strand drain wire.
5. Outer Sheath H : HFFR Sheath (EN 50290-2-27), RAL 5015 Blue, RAL 9005 Black
General Features
Flame Retardent
(For Single Cable)
IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2
Flame Retardent (For a Bunch of Cable) IEC 60332-3-24, EN 60332-3-24, VDE 0482-332-3-24
Determination of (Test of determination of flaming droplets) IEC 60332-1-3, EN 60332-1-3, VDE 0482-332-1-3
Halogen Acid Gas Test IEC 60754-1, EN 50267-2-1, VDE 0482-267-2-1
Acidic (Corrosive)
Gas Test
IEC 60754-2, EN 50267-2-2, VDE 0482-267-2-2
Smoke Density Test IEC 61034-2, EN 61034-2, VDE 0482-1034-2
Insulation Continuity Test (FE-) IEC 60331-21, VDE 472 part 814
Circuit Integrity With Shock (PH) EN 50200, VDE 0482-200
Oil Resistance ICEA S-82-552
Technical Properties
Temperature Range Sabit -30 °C …. +90 °C / Hareketli -5 °C …. +90 °C
Min. Bending Radius 10xD
Documents
 RE-2G(St)H-CI MC FE-180 PH90

admin