RE-2Y(St)HSWAH-fl MC RE-2X(St)HSWAH-fl MC

EN 50288-7
Multi-Core, Overall Screen, Round Steel Wire Armour Signalling Cables300 V-500 V

RE-2Y(St)HSWAH-fl MC<br />
RE-2X(St)HSWAH-fl MC

Application
These cables are generally employed in instrumentation and control systems, analog and digital signal transmission of chemical and petrochemical industrial
premises, power plants, natural gas and petroleum industries, etc. Direct connection is not permitted under ambient with a low impedance sources. Cables with blue sheaths
are suitable for security system applications. Furthermore, these cables can directly be buried in the soil. They are suitable in dry and wet indoor and outdoor installations.
Construction
1. Inner Conductor Electrolytic stranded annealed copper wire (IEC 60228, Class 2)
2. Insulation 2Y : PE (EN 50290-2-23)
2X : XLPE (EN 50290-2-29)
3. Lay-Up Cores are twisted in layers. Fixed with PES tape.
4. Lay-Up (St) %100 Coverage AL-PES tape ve 0,50 mm² (7×0,30 mm) screened with tinned strand drain wire.
5. Lay-Up H : HFFR Sheath (EN 50290-2-27)
6. Armouring SWA : Round galvanized steel wire armour• HFFR Sheath (EN 50290-2-27), RAL 9005 Black, RAL 5015
7. Outer Sheath H : Blue veya RAL 7001 Grey
General Features
Flame Retardent
(For Single Cable)
IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2
Flame Retardent (For a Bunch of Cable) IEC 60332-3-24, EN 60332-3-24, VDE 0482-332-3-24
Determination of (Test of determination of flaming droplets) IEC 60332-1-3, EN 60332-1-3, VDE 0482-332-1-3
Halogen Acid Gas Test IEC 60754-1, EN 50267-2-1, VDE 0482-267-2-1
Acidic (Corrosive)
Gas Test
IEC 60754-2, EN 50267-2-2, VDE 0482-267-2-2
Smoke Density Test IEC 61034-2, EN 61034-2, VDE 0482-1034-2
Oil Resistance Only valid for Black sheath cables..
Technical Properties
PE (2Y) / XLPE (2X)
Temperature Range Fixed -30 °C …. +70 °C / Flexible -5 °C …. +50 °C / Fixed -30 °C …. +90 °C / Flexible -5 °C …. +50 °C
Min. Bending Radius 10xD