Ref. Std. VDE 0815 Fire Resistant, Internal Installation Communcation and Fire Alarm Cables (Mica Tape Insulated) |
Application
These cables can function in case of fire Halgen Free, flame retardant, low smoke denstiy, Acidic (Corrosive) Gas Test, air ports, hospitals, metro, subway stations, shopping centers, high rise buildings, hotels, industrials plants and so on. signal and communication cables are used as an emergency circuits. |
Construction
1. | Inner Conductor | Electrolytic mono annealed copper (EN 60228, Class 1) |
2. | Insulation | Mica tape On HFFR insulation (EN 50290-2-26) Core colors will be suitable to VDE 0815. (Table 1) Up to 4 pairs can produce different core color combination |
3. | Lay-Up | Dual twisted cores are twisted together in 4-units, 4 units twisted in layers. |
4. | Flame Barrier | To increase the flame resistance of twisted cores, wrapped with special flame retardant glass fiber tape. |
5. | Outer Sheath | HFFR (EN 50290-2-27, VDE0207 HM2), RAL 2003 Orange |
General Features
Flame Retardent (For Single Cable) |
IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2 | |
Flame Retardent (For a Bunch of Cable) | IEC 60332-3-24, EN 60332-3-24, VDE 0482-332-3-24 | |
Determination of (Test of determination of flaming droplets) | IEC 60332-1-3, EN 60332-1-3, VDE 0482-332-1-3 | |
Halogen Acid Gas Test | IEC 60754-1, EN 50267-2-1, VDE 0482-267-2-1 | |
Acidic (Corrosive) Gas Test |
IEC 60754-2, EN 50267-2-2, VDE 0482-267-2-2 |
|
Smoke Density Test | IEC 61034-2, EN 61034-2, VDE 0482-1034-2 | |
Insulation Continuity Test (FE-) | IEC 60331-21, VDE 472 part 814 | |
Circuit Integrity With Shock (PH) | EN 50200, VDE 0482-200 |
Technical Properties
0,8 mm / 1,0 mm / 1,5 mm² / 2,5 mm² | ||
Temperature Range | -30 °C …. +70 °C | |
Operating Voltage | Max. 300 V | |
Test Voltage | Core/core, 1500 V | |
Min. Bending Radius | 10xD |
Documents
J-HH…Bd FE-180 PH120 |