Ref. Std. VDE 0812 Fire Resistant, Double Twist, AL Foil Screened, Sİgnal and Control Cables (Mica Tape Insulated) |
Application
These cables can function in case of fire Halgen Free, flame retardant, low smoke denstiy, Acidic (Corrosive) Gas Test, air ports, hospitals, metro, subway stations, shopping centers, high rise buildings, hotels, industrials plants and so on. signal and communication cables are used as an emergency circuits. |
Construction
1. | Inner Conductor | Electrolytic stranded annealed copper wire (EN 60228, Class 5) |
2. | Insulation | Mica tape On HFFR insulation (EN 50290-2-26). Up to 4 pair core colours will be suitable according to DIN 4710. After 4 pairs can produce different core colours combinations. |
3. | Lay-Up | Colors are twisted in pair and bend in the layers. |
4. | Flame Barrier | To increase the flame resistance of twisted cores, wrapped with special flame retardant glass fiber tape. |
5. | Screen | They are screened with AL-PES tape and twisted tin-copper coverage helical wound drain wire. |
6. | Outer Sheath | HFFR (EN 50290-2-27), RAL 2003 Orange |
General Features
Flame Retardent (For Single Cable) |
IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2 | |
Flame Retardent (For a Bunch of Cable) | IEC 60332-3-24, EN 60332-3-24, VDE 0482-332-3-24 | |
Determination of (Test of determination of flaming droplets) | IEC 60332-1-3, EN 60332-1-3, VDE 0482-332-1-3 | |
Halogen Acid Gas Test | IEC 60754-1, EN 50267-2-1, VDE 0482-267-2-1 | |
Acidic (Corrosive) Gas Test |
IEC 60754-2, EN 50267-2-2, VDE 0482-267-2-2 |
|
Smoke Density Test | IEC 61034-2, EN 61034-2, VDE 0482-1034-2 | |
Insulation Continuity Test (FE-) | IEC 60331-21, VDE 472 part 814 | |
Circuit Integrity With Shock (PH) | EN 50200, VDE 0482-200 |
Technical Properties
Temperature Range | Fixed -30 °C …. +70 °C / Flexible -5 °C …. +50 °C | |
Operating Voltage | 300 V | |
Test Voltage | Core-core 1200 V, core-Screen 1200 V | |
Min. Bending Radius | Fixed 7,5xD / Flexible 15xD |
Documents
LIH(St)H-TP FE-180 PH120 |