HFFR, Filled and Screen Control Cables |
Application
Such cables are suitable for use in machine production for measuring, imaging and control purposes, in power stations, engineering projects and HVAC and similar electrical systems under dry or moist ambient, in particular suited to the industrial environments. Theese cables not used open air, outdoor environments. and similar electrical systems under dry or moist ambient, in particular suited to the industrial environments. Theese cables not used open air, outdoor environments |
Construction
1. | Inner Conductor | Electrolytic stranded annealed copper wire (IEC 60228, VDE0295, HD383, Class 5) |
2. | Insulation | HFFR (EN 50290-2-26, VDE0207-HI2) |
3. | Lay-Up | According to VDE 293 insulated cores twisted in layers. From 3c ores Yellow / Green line is drain core. |
4. | Inner Sheath | HFFR sheath should be peeled off easily without gluing onto the insulation. |
5. | Screen | Tinned copper wire Braid Screen |
6. | Outer Sheath | HFFR (EN 50290-2-27, VDE0207-HM2), RAL 7001, Grey |
General Features
Flame Retardent (For Single Cable) |
IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2 | |
Flame Retardent (For a Bunch of Cable) | IEC 60332-3-24, EN 60332-3-24, VDE 0482-332-3-24 | |
Determination of (Test of determination of flaming droplets) | IEC 60332-1-3, EN 60332-1-3, VDE 0482-332-1-3 | |
Halogen Acid Gas Test | IEC 60754-1, EN 50267-2-1, VDE 0482-267-2-1 | |
Acidic (Corrosive) Gas Test |
IEC 60754-2, EN 50267-2-2, VDE 0482-267-2-2 | |
Smoke Density Test | IEC 61034-2, EN 61034-2, VDE 0482-1034-2 |
Technical Properties
Temperature Range | Fixed -30 °C …. +70 °C Flexible 0 °C …. +50 °C | |
Min. Bending Radius | Fixed 7,5xD Flexible 15x |
Documents
NHSLHCH (HSLHCH)-JZ |