Ref. Std. HD 21.13 S1, DIN VDE 0281 part 13 Oil Resistance PVC Sheath Control Cables |
Application
Such cables are suitable for use in machine production for measuring, imaging and control purposes, in power stations, engineering projects and HVAC and similar electrical systems under dry or moist ambient, in particular suited to the industrial environments. Theese cables not used open air, outdoor environments. |
Construction
1. | Inner Conductor | Electrolytic stranded annealed copper wire (IEC 60228, VDE0295, HD383, Class 5) |
2. | Insulation | PVC (EN 50290-2-21 TI52, VDE 0207-YI2) |
3. | Lay-Up | According to DIN 47100 colors insulated cores twisted in layers |
4. | Outer Sheath | PVC Sheath (EN 50290-2-22 TM51, VDE 0207-YM1), RAL 7001, Grey |
General Features
Flame Retardent (For Single Cable) |
IEC 60332-1, EN 60332-1, VDE 0482-332-1 | |
Oil Resistance | IEC 60811-2-1, EN 60811-2-1, HD 505.2.1 |
Technical Properties
Temperature Range | Fixed -40 °C …. +70 °C Flexible -5 °C …. +70 °C | |
Operating Voltage | 300/500 V | |
Test Voltage | 2000 V, 5 dk | |
Short Circuit Temperature Range | Max. 160 °C | |
Min. Bending Radius | 10xD |
Documents
H05VV5-F / (NYSLYÖ-JZ) |