H05VV5-F / (NYSLYÖ-JZ)

Ref. Std. HD 21.13 S1, DIN VDE 0281 part 13
Oil Resistance PVC Sheath Control Cables

H05VV5-F / (NYSLYÖ-JZ)

Application
Such cables are suitable for use in machine production for measuring, imaging and control purposes, in power stations, engineering projects and HVAC
and similar electrical systems under dry or moist ambient, in particular suited to the industrial environments. Theese cables not used open air, outdoor environments.
Construction
1. Inner Conductor Electrolytic stranded annealed copper wire (IEC 60228, VDE0295, HD383, Class 5)
2. Insulation PVC (EN 50290-2-21 TI52, VDE 0207-YI2)
3. Lay-Up According to DIN 47100 colors insulated cores twisted in layers
4. Outer Sheath PVC Sheath (EN 50290-2-22 TM51, VDE 0207-YM1), RAL 7001, Grey
General Features
Flame Retardent
(For Single Cable)
IEC 60332-1, EN 60332-1, VDE 0482-332-1
Oil Resistance IEC 60811-2-1, EN 60811-2-1, HD 505.2.1
Technical Properties
Temperature Range Fixed -40 °C …. +70 °C Flexible -5 °C …. +70 °C
Operating Voltage 300/500 V
Test Voltage 2000 V, 5 dk
Short Circuit Temperature Range Max. 160 °C
Min. Bending Radius 10xD