LIHH FE-180 PH120

Ref. Std. VDE 0812
Fire Resistant, Signal and Control Cables (Mica Tape Insulated)

LIHH FE-180 PH120

Application
These cables can function in case of fire Halgen Free, flame retardant, low smoke denstiy, Acidic (Corrosive) Gas Test, air ports, hospitals, metro, subway
stations, shopping centers, high rise buildings, hotels, industrials plants and so on. signal and communication cables are used as an emergency circuits.
Construction
1. Inner Conductor Electrolytic stranded annealed copper wire (EN 60228, Class 5)
2. Insulation Mica tape On HFFR insulation (EN 50290-2-26). Up to 8 cores, colors of cores are be suitable DIN 47100. After
8 core can use numbered core.
3. Lay-Up Insulated cores are twisted in layers.
4. Flame Barrier To increase the flame resistance of twisted cores, wrapped with special flame retardant glass fiber tape.
5. Outer Sheath HFFR (EN 50290-2-27) , RAL 2003 Orange
General Features
Flame Retardent
(For Single Cable)
IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2
Flame Retardent (For a Bunch of Cable) IEC 60332-3-24, EN 60332-3-24, VDE 0482-332-3-24
Determination of (Test of determination of flaming droplets) IEC 60332-1-3, EN 60332-1-3, VDE 0482-332-1-3
Halogen Acid Gas Test IEC 60754-1, EN 50267-2-1, VDE 0482-267-2-1
Acidic (Corrosive)
Gas Test
IEC 60754-2, EN 50267-2-2,
VDE 0482-267-2-2
Smoke Density Test IEC 61034-2, EN 61034-2, VDE 0482-1034-2
Insulation Continuity Test (FE-) IEC 60331-21, VDE 472 part 814
Circuit Integrity With Shock (PH) EN 50200, VDE 0482-200
Technical Properties
Temperature Range Fixed -30 °C …. +70 °C / Flexible -5 °C …. +50 °C
Operating Voltage 300 V
Test Voltage Core-core 1200 V
Min. Bending Radius Fixed 7,5xD / Flexible 15xD